Most check valves are selected by size and Class to match the size and Class of the pipe. While this is convenient and simple, it is not necessarily the best way to choose the correct check valve. This article looks to examine the consequences of selecting check valves the way most currently are and offers a different method of selection, why it can lead to far higher and longer performance and the supporting formulas and fluid dynamics that one can use to prove it yourself.
There are several different types of check valves but all are required to prevent back flow; that is how their other name came about non-return valves or NRVs. They do this largely independent of any external device or implement. Instead they rely primarily on the piping systems internal factors like cessation of flow and flow reversal; some with assistance only from gravity and some with internal springs. Simply put; all check valves open by flow and close when flow stops.
Unlike other types of valves that are operated manually or by automation and are placed in their operating positions like fully open or fully closed; check valves require sufficient flow velocity to open fully and without knowing some basics like flowrate, pipe ID and specific volume; you cannot know if that condition exists by simply knowing the pipe size.
The six distinct types of check valves:
a. Swing Check (bonneted unassisted gravity swing check; generally RF flanged)
b. Dual Disc Check (dual flapper wafer check; generally wafer flanged)
c. Wafer Check (single flapper wafer check; generally wafer flanged)
d. Axial Flow (axial disc or centre-guided non-slam check; generally RF flanged)
e. Piston Check (piston check; generally RF flanged above 1 (25mm)
f. Ball Checks (also plug checks, generallyRF flanged, screwed or SW)
We shall focus on the most common of the check valves the Swing Check. It is available in a very wide variety of sizes, pressure classes and materials. There are three basic variations as shown in examples a, b and c below.
a) Bonneted unassisted gravity swing check
b) Dual Disc Wafer Body
c) Single Flapper Wafer Body
All styles of check valve operate under the same principals. The traditional method of choosing a body size to match the pipe size will often lead to a valve that is not fully open at minimum or even normal flowrates. While this practice is widely used, in most cases this will not lead to best performance or the lowest cost of ownership.
The reason is similar for control valves. To obtain a properly sized control valve you must solve for the required Cv (sizing the valve or orifice); and once that is solved, (usually as Cv Min, Cv Norm and Cv Max) for the flowrates at the process minimum, normal and maximum flow conditions, you select the proper body size for the trim (internals) you have determined best suits those Cv values.
Cv, the flow coefficient of a device (in SI units it is the Kv flow factor) is a relative measure of its efficiency at permitting fluid flow. It describes the relationship between the energy (as pressure drop) across an orifice, valve or other piping component and the corresponding flowrate.
The installed Cv of any valve is the Cv that occurs when the valve is operating in the piping system and the process is running. The published Cv of any check valve is irrelevant if it isnt fully opened. As most check valves offer one inlet and internal trim dimension per size and Class, the chances are low that it will match the application it will be installed in and without sizing, will only be apparent after installation when it may be too late.
The diagram above shows a typical bonneted unassisted gravity swing check with a normal flowrate of water at 7 ft/sec (2.2 m/sec) and a same pipe-sized venturi inlet single flapper wafer swing check under the same flow conditions.
The difference is that the flow is insufficient to fully open the gravity swing check and it fails to open enough to produce the Cv it is capable of. This also has a detrimental effect on the service life of the valve as it means the flapper will be unstable and moving constantly, subject to wear and tear; and a shorter life than could be expected if it were properly sized.
The single flapper wafer check takes the 7 ft/sec water and momentarily increases the velocity at the disc through a decrease in orifice size to lift the flapper fully, a position where it is stable and achieves the highest installed Cv. This requires an engineered and sized inlet orifice, what we call a Venturi inlet.
If we install line-sized check valves that have not been sized for low and normal flow conditions and they do not fully open the disc, we should expect shortened life. This is due to the mechanical movement of the disc as the flowrate varies, however slightly, during the valves service life and the turbulence and the vibration that result from it. If we installed properly sized check valves for minimum flow rates and obtain 100% Cv, then we will always achieve 100% Cv on the higher flowrates. Once fully open we should expect longer life through the flappers stable position 100% open is 100% open.
In order to properly size a check valve, you must determine the minimum velocity required to fully lift the disc. Then find the mean velocity of flow in the piping system and ensure it is greater than or equal to the minimum required velocity.
Variables:
v = mean velocity of flow (ft/s)
r = weight density of fluid (lb/ft3)
V = specific volume of fluid (ft3/lb)
Q= rate of flow (usgpm)
d = internal diameter (in)
To determine the minimum velocity required to fully lift the disc of a wafer body swing check valve, we use the following formula:(note we use Hy-Grade Inc, series T venturi inlet single flapper for the formula as they have extensive flow testing results)
vmin = 55 (V), where V = 1/ r
The company is the world’s best Industrial Swing Check Valve supplier. We are your one-stop shop for all needs. Our staff are highly-specialized and will help you find the product you need.
Determine the mean velocity of flow in the pipe using the following formula:
v = 0. (Q / d2)
Example:
Given: A venturi inlet single flapper check valve is required for an 8 Class 150 (Schedule 40) pipe carrying 60ºF water at 650 US gallons per minute.
r = 62.364 lb/ft3
d4 Schedule 40 = 4.026 in
d6 Schedule 40 = 6.065 in
d8 Schedule 40 = 7.981 in
d10 Schedule 40 = 10.020 in
d12 Schedule 40 = 11.938 in
Find: Proper sized venturi inlet single flapper wafer check valve for the application
1. V = 1/62.364 = 0. ft3/lb
vmin = 55 (V) = 55 (0.) = 6.96 ft/s
2. v = 0. (650 / 7.) = 4.17 ft/s
3. Since v is less than vmin, an 8 valve will be too large. Now try a 6:
v = 0. (650 / 6.) = 7.22 ft/s
Based on the calculations above, a 6 HyGrade T series check valve should be installed in this 8 Class 150 line because the velocity of 7.22 ft/s is higher than 6.96 ft/s and the valve will be fully opened. Since all components of Hy-Grade valves are machined in-house, Hy-Grade can custom make a valve with 6 internals (or virtually any inlet venturi) to fit 8 flanges to eliminate the need of piping reducers.
The data required to properly size check valves may not be readily available, but the effort necessary to obtain it will more than be repaid by the significant improvement in service life and operational performance. Our analysis of many check valve installations demonstrates with a high degree of confidence that the majority of check valves are oversized.
In summary, when you properly size check valves for the application you will often or always gain several advantages:
Smaller valves that cost less
Longer lived valves due to flapper stability
Higher performance due to less wear and
tear on the flapper and seat
Lower downstream piping issues
About the Author
Ross, President of CGIS, is a voting member of ASTM on the G04 Gaseous Oxygen Committee and serves on Manufacturers Standardization Society (MSS) as a task force member on C-114 Steel Valves and C-409 Knife Gates. Currently Ross is a member of the task force to write and publish a new Standard on Severe Service Valve Testing.
*This article was originally published in Valve World Americas, March issue.
The slanted seat check valve also offers enhanced resistance to water hammer. The valve has a double eccentric shaft position as well as an increased seating angle. This yields a shorter valve stroke, thus reducing the time taken for the door to close.
Hydraulic dampers are recommended, especially when the valves are installed on a pumping station where high frequency opening and closing of the valve is required. The valve disc closes quickly over the first 85% of its angular travel before meeting the hydraulic damper. The damper then dissipates the kinetic energy of the disc and forces it to open slightly. The disc closes until it contacts the damper again and this cushions the disc until it returns to its fully closed position, sealing the valve. This function greatly reduces the onset of water hammer due to the damped and controlled method of valve closure.Hydraulic dampers are recommended, especially when the valves are installed on a pumping station where high frequency opening and closing of the valve is required. The valve disc closes quickly over the first 85% of its angular travel before meeting the hydraulic damper. The damper then dissipates the kinetic energy of the disc and forces it to open slightly. The disc closes until it contacts the damper again and this cushions the disc until it returns to its fully closed position, sealing the valve. This function greatly reduces the onset of water hammer due to the damped and controlled method of valve closure.
For more details, please see our slanted seat check valve product information.
Nozzle check valves are designed with the valve disc connected to the stem which is guided on the central horizontal axis. A spring is positioned between the disc and the diffuser sleeve. When flow enters the valve, the hydraulic force exerted onto the front face reacts against the spring, causing the spring to compress and allow the valve to open. When the flow stops, the spring forces the disc to return to the closed position.
Due to the spring-assisted closure and the short linear valve stroke, the nozzle check valve is one of the quickest acting check valves available and is commonly used in pumped systems where water hammer is a potential concern. Because the disc is constantly in the direct line of flow, the head loss characteristics of this valve are higher compared to that of conventional swing check valves.
For more details, please see our nozzle check valve product information.
In order to choose the right check valve for your application, several selection criteria should be considered. First, however, there is not one type of check valves being the best choice for all applications, and the selection criteria may not be equally important for all cases. Some of the things you may need to consider are fluid compatibility, flow characteristics, head loss, non-slam characteristics and total cost of ownership.
All check valves referred to in this article are designed for water and treated wastewater applications, but using the valves for raw wastewater/sewage applications may cause some issues. When selecting a valve for these fluids, you should consider how the presence of solids may potentially affect operation of the valve.
If a check valve closes very fast, it may prevent slamming against upstream equipment such as pumps. However, the rapid closure will not protect against the surges caused by pumps being started and shut down. If the valve opens (and closes) quickly, the flow will change rapidly and thus increase likeliness of surge occurrence.
Head loss is, among other things, a function of fluid velocity. The head loss through a valve is determined by the internal design of the valve and the opening degree. When a valve is designed with a restricted (narrowed) opening compared to the pipeline, the velocity will increase through the valve, increasing the head loss as a result. Vice versa, if a valve is designed with less restriction and bore is equal size to the pipeline, the head loss will be smaller, and the valve will in practice not affect the overall head loss of the system. There are a number of values for head loss, amongst others zeta values, Kv and Kvs values.
The costs for your check valve consist of more than just the purchase price. For some installations, the most important costs may be purchasing and installation, but in other cases, maintenance or energy costs may be equally or even more important. Also protecting more valuable equipment such as e.g. pumps has to be considered, and looking at the valve performance will be crucial. When considering costs as a selection criterion for your check valve, the total costs over the life of the valve should be considered. In general, the simpler the valve construction is, the lower are the maintenance requirements. The higher the Kv value, the lower the energy consumption. The higher the performance, the better the protection ability.
Check valve slam can affect pressure surges in a negative way. First step of the process is when the pump stops, starting the pressure surge. Second step is, when the flow is reversed, slamming against the fully closed check valve. If the check valve closes too fast, the kinetic energy is turned into high pressure, stressing the pipes, and causing high noise.
A slam sounds like if the disc or the ball from the check valve is hitting the seat and can make quite some noise. However, the sound is not caused by the physical closing but by a sound wave arising from a pressure spike stretching the pipe wall.
To prevent the occurrence of check valve slam, the valve should close in a controlled way and slower when near closed position. For a check valve to close slowly, it requires additional ancillary equipment, such as hydraulic dampers, which act as a cushion to the valve door, as it comes into its seated position. This slower closure allows the fluid to pass through the check valve until it closes, causing less kinetic energy turning into high pressure, and thus less energy to feed and maintain the surge. Consideration must be given to the upstream pump to ensure that it is suitable for reverse spin and flow.
As swing check valves have the disc in the flow stream, helping with rapid closure, they have better non-slam characteristics. However, today many pumps are frequency converted, enabling them to adjust the start-up and closure time to avoid water hammer.
Contact us to discuss your requirements of High Pressure Flanged Ball Valves. Our experienced sales team can help you identify the options that best suit your needs.